6 Commissioning, operation

Wire cross-section:

- Single wire: 0.13 ... 2.5 mm

2

- End splices: 0.13 ... 1.5 mm

2

- Ground screw, inside: 0.13 ... 2.5 mm²

- Ground screw, outside: 0.13 ... 4 mm²

- When using DIN 175301-803 A angular connector 1.5 mm² (only via end splices)

When using an M12 x 1 (4-pin) circular connector, the mating connector is supplied

by the customer. It is important to ensure the matching design from the connector

manufacturer.

6.2.2 Making the electrical connection

CAUTION!

Ingress of moisture.

Moisture can destroy the process transmitter.

- Protect the opened process transmitter against moisture.

1. Screw off the case head cover by hand and pull out the display and operating unit or

push-on cap.

2. Pass the connection cable through the cable gland and connect it.

- For pin assignment see chapter 6.2.3 “pin assignments”.

- Ground the process transmitter via the process connection or connect with the

equipotential bonding via the external grounding screw.

3. Tighten the cable gland.

- Recommended tightening torque 1.5 Nm

- Check that the seals are correctly seated in order to guarantee the ingress

protection.

- Ensure that no moisture can enter at the cable end.