WIKA operating instructions process transmitter, model UPT-2x

14068347.01 06/2014 GB/D

GB

14. Faults

14. Faults

In the event of any faults, first check whether the process transmitter is mounted

correctly, mechanically and electrically. For instruments with display and operating units,

the error code with error text will be displayed in the event of a failure.

Faults

Causes

Measures

Display does not indicate

anything

Instrument is not mounted

correctly

Install the electrical connec-

tion and/or the display and

operating unit correctly

Error code Error text

Causes

Measures

E001

Hardware fault

Lack of communication

Restart the instrument.

Return the instrument.

E002

Sensor missing

Communication to the

sensor faulty

Restart the instrument.

Return the instrument.

E003

Sensor faulty

Pressure status sensor faulty Restart the instrument.

Return the instrument.

E004

Characteristic curve

error

Overflow in calculation chain Restart the instrument.

Switch to a linear character-

istic curve.

Check the inputs.

Return the instrument.

E005

Temperature sensor

Temperature sensor faulty

Restart the instrument

Return the instrument

E006

1)

Overpressure sensor Overload pressure sensor

Restart the instrument

Depressurise the instrument

(ambient pressure) and

restart

Return the instrument

E007

Sensor temperature

Temperature exceeded at

the pressure sensor, limit

monitoring in the electronics

Return the instrument

1) Error message can also appear when the pressure is greater than the nominal pressure range.