8. Configuration without display and operating unit

8. Configuration without display and operating unit

8.1 Performing a mounting correction (offset)

The mounting correction corrects a zero offset in the output signal by defining a new

zero point. The zero offset is caused by the mounting position.

Correction range: ±20 % of maximum measuring range

Required tool: Multimeter (ammeter)

1. Screw off the case head cover and pull out the push-on cap.

2. Press [Zero] for approx. 2 s (e.g. with measuring tip of a multimeter).

Mounting correction successful: Control diode lights up for 2 s.

Mounting correction unsuccessful: Control diode blinks 5 times.

3. Check the output signal as follows.

CAUTION!

Incorrect connection.

A short circuit will destroy the process transmitter.

- Ensure that the multimeter does not come into contact with the positive

power supply terminal.

Set the multimeter to current measurement.

Connect the positive measuring line of the multimeter to the test contact.

Connect the negative measuring line of the multimeter to the negative power

supply terminal.

Control diode

Mounting correction, [Zero] key

Test contact

Positive power supply terminal +

Negative power supply terminal