8. Configuration without display and operating unit

8. Configuration without display and operating unit

8.1 Performing a mounting correction (offset)

The mounting correction corrects a zero offset in the output signal by defining a new

zero point. The zero offset is caused by the mounting position.

Correction range: ±20 % of maximum measuring range

Required tool: Multimeter (ammeter)

1. Screw off the case head cover and pull out the push-on cap.

2. Press [Zero] for approx. 2 s (e.g. with measuring tip of a multimeter).

Mounting correction successful: Control diode lights up for 2 s.

Mounting correction unsuccessful: Control diode blinks 5 times.

3. Check the output signal as follows.

CAUTION!

Incorrect connection.

A short circuit will destroy the process transmitter.

- Ensure that the multimeter does not come into contact with the positive

power supply terminal.

■

Set the multimeter to current measurement.

■

Connect the positive measuring line of the multimeter to the test contact.

■

Connect the negative measuring line of the multimeter to the negative power

supply terminal.

Control diode

Mounting correction, [Zero] key

Test contact

Positive power supply terminal +

Negative power supply terminal –