Configuration via display and operating unit, Configuring the measuring task, Configuring pressure measurement – WIKA UPT-21 Benutzerhandbuch

Seite 31

Advertising
background image

31

WIKA operating instructions process transmitter, model UPT-2x

14068347.01 06/2014 GB/D

GB

9. Configuration via display and operating unit

9. Configuration via display and operating unit

9.1 Configuring the measuring task

9.1.1 Configuring pressure measurement

1. Open the operating menu with [↵].

Select “Basic setting” and confirm with [↵].

2. Select “Application” and confirm with [↵].

3. Select “Pressure” and confirm with [↵].

4. Select “Unit” and confirm with [↵].

5. Select pressure unit and confirm with [↵].

Pressure unit is set.

6. Go back one menu level using [ESC].

Select “Mode” and confirm with [↵].

7. Select “Pressure” and confirm with [↵].

Mode is set.

8. Scale the measuring range.

See chapter 9.3 “Scaling the measuring range”.

9. Perform a mounting correction.

See chapter 9.5 “Mounting correction (offset)”.