Configuration via display and operating unit, Configuring the measuring task, Configuring pressure measurement – WIKA UPT-21 Benutzerhandbuch
Seite 31

31
WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
9. Configuration via display and operating unit
9. Configuration via display and operating unit
9.1 Configuring the measuring task
9.1.1 Configuring pressure measurement
1. Open the operating menu with [↵].
Select “Basic setting” and confirm with [↵].
2. Select “Application” and confirm with [↵].
3. Select “Pressure” and confirm with [↵].
4. Select “Unit” and confirm with [↵].
5. Select pressure unit and confirm with [↵].
Pressure unit is set.
6. Go back one menu level using [ESC].
Select “Mode” and confirm with [↵].
7. Select “Pressure” and confirm with [↵].
Mode is set.
8. Scale the measuring range.
See chapter 9.3 “Scaling the measuring range”.
9. Perform a mounting correction.
See chapter 9.5 “Mounting correction (offset)”.