47

WIKA operating instructions process transmitter, model UPT-2x

14068347.01 06/2014 GB/D

GB

11. Detail setup

11.7 Setting the HART

communication

11.7.1 Setting the short address (multidrop mode)

Setting range: 0 ... 63

1. Open the operating menu with [↵].

Select “Detail setup" and confirm with [↵].

2. Select “HART” and confirm with [↵].

3. Select “Short addr.” and confirm with [↵].

4. Change digit using [▲] [▼] and confirm with [↵]. The

cursor moves to the next digit. Repeat for each digit.

Short address is set.

11.7.2 Activating/deactivating constant current

The constant current affects the output of current values, e.g. in the additional

display

1. Open the operating menu with [↵].

Select “Detail setup" and confirm with [↵].

2. Select “HART” and confirm with [↵].

3. Select “Cons. current” and confirm with [↵].

4. Activate/deactivate constant current.

Select “on” or “off” and confirm with [↵].

Constant current is activated/deactivated.