9. Configuration via display and operating unit
9.1.2 Configuring level measurement
1. Open the operating menu with [↵].
Select “Basic setting” and confirm with [↵].
2. Select “Application” and confirm with [↵].
3. Select “Level” and confirm with [↵].
4. Select “Unit” and confirm with [↵].
5. Select length unit and confirm with [↵].
Length unit is set.
6. Select “Density” and confirm with [↵].
7. Select “Density unit” and confirm with [↵].
8. Select density unit and confirm with [↵].
Density unit is set.
9. Select “Density value” and confirm with [↵].
10. Set digit using [▲] [▼] and confirm with [↵]. The
cursor moves to the next digit. Repeat for each digit.
Density value is set.
11. Go back two menu levels using [ESC].
Select “Mode” and confirm with [↵].
12. Select “Level” and confirm with [↵].
Mode is set.
13. Perform a mounting correction.
See chapter 9.5 “Mounting correction (offset)”.