3 creating alarms, Creating alarms, Project example – Lenze VisiWinNet VisiWinNET Smart Benutzerhandbuch

Seite 209

Advertising
background image

Project example

Configuring the alarm system

Creating alarms

4

l

209

SHP−VWNS DE/EN 6.1

4.7.3

Creating alarms

Alarm for "Grp1" alarm group

1. In order to create the two alarms in alarm group Grp1, select alarm group Grp1 in

Project Explorer, right−click in the client area and, in the context menu, select the
New command.

2. Specify the following properties:

Properties for alarms

No. Tab/Property

Value

Comments

1

General

Name

Msg1

Text

MessageSource; Bit 0

Click [...], then click the command
button with the binoculars, select
Variable MessageSource and specify
bit number 0

Event variable

MessageSource

Bit No. of event variable

0

Priority

1

Extended

Status variable

MessageState

Bit No.of status variable

0

2

General

Name

Msg2

Text

MessageSource; Bit 1

See above

Event variable

MessageSource

Bit No. of event variable

1

Priority

2

Extended

Status variable

MessageState

Bit No.of status variable

4