Gb 3. specifications / 4. design and function, Design and function – WIKA DI25 Benutzerhandbuch

Seite 14

Advertising
background image

14

WIKA operating instructions digital indicator, model DI25

14076218.01 12/2013 GB/D

GB

3. Specifications / 4. Design and function

No. Designation

Description

1

PV

Actual value display

The actual value (PV = process variable) is

displayed with a red LED display.

2

SV

Setting value display

Shows the setting values (SV) with a green LED

display.

3

A1

Display alarm output 1

The red LED lights up when alarm output 1 is ON.

4

A2

Display alarm output 2

The red LED lights up when alarm output 2 is ON.

5

A3

Display alarm output 3

The red LED lights up when alarm output 3 is ON.

6

HOLD Diplay HOLD function

The yellow LED lights up when the HOLD function

is activated.

7

A1

Display alarm value, alarm output 1

The green LED lights up when the SV display

shows the alarm value of alarm 1.

8

A2

Display alarm value, alarm output 2

The green LED lights up when the SV display

shows the alarm value of alarm 2.

9

A3

Display alarm value, alarm output 3

The green LED lights up when the SV display

shows the alarm value of alarm 3.

10

△ Key

Increases a numerical value or selects a setting

parameter.

11

▽ Key

Decreases a numerical value or selects a setting

parameter.

12

MODE key

Selects the setting mode or stores the selected

setting parameter.

13

FAST key

The setting values change faster if the FAST key is

pressed together with the △ or ▽ key.

For further specifications see WIKA data sheet AC 80.02 and the order documentation.

4. Design and function

4.1 Short description

The digital indicator DI25 is a multi-functional digital indicator for a wide range of

measuring requirements. The multi-function input has 18 different input configurations,

which can be selected via the rear connections and also by selection of the appropriate

input signal within the instrument configuration. This way it is possible

to connect transmitters with current or voltage signals, and both resistance thermo-

meters or thermocouples to the same instrument.

The measured value can be retransmitted for further processing via an analogue actual

value 4 ... 20 mA output (standard) or via an RS-485 serial interface (optional). Other

analogue actual-value output signals are also available as options. The basic version of

the DI25 indicator features three alarm outputs. Instruments with the optional 24 V trans-

mitter power supply have two alarm outputs available.

With the high ingress protection of the fascia (IP 66), the DI25 digital indicator can also

be used under extreme operating conditions. All configuration and programming can be

carried out through the front-panel keys.