Gb 6. commissioning, operation, Setting ranges alarm types, Setting ranges of the input configuration – WIKA DI25 Benutzerhandbuch
Seite 27

27
WIKA operating instructions digital indicator, model DI25
14076218.01 12/2013 GB/D
GB
6. Commissioning, operation
Setting ranges alarm types
Alarm type
Setting range
High alarm
Start value to end value of the input configuration
Low alarm
Start value to end value of the input configuration
High alarm with standby
Start value to end value of the input configuration
Low alarm with standby
Start value to end value of the input configuration
High/low alarm
none
The high/low alarm ist only available for alarm A3.
Once the high/low alarm is selected, the settings in connection with A3
(A3 alarm value, A3 switch behaviour, A3 hysteresis, A3 delay time) will not be
indicated.
Setting ranges of the input configuration
TCs and RTDs
°C
°F
K
-200 ... +1,370 °C
-320 ... +2,500 °F
-199.9 ... +400.0 °C
-199.9 ... +750.0 °F
J
-200 ... +1,000 °C
-320 ... +1,800 °F
R
0 ... 1,760 °C
0 ... 3,200 °F
S
0 ... 1,760 °C
0 ... 3,200 °F
B
0 ... 1,820 °C
0 ... 3,300 °F
E
-200 ... +800 °C
-320 ... +1,500 °F
T
-199.9 ... +400.0 °C
-199.9 ... +750 °F
N
-200 ... +1,300 °C
-320 ... +2,300 °F
PL-II
0 ... 1,390 °C
0 ... 2,500 °F
C (W/Re5-26)
0 ... 2,315 °C
0 ... 4,200 °F
Pt100
-199.9 ... +850.0 °C
-199.9 ... +999.9 °F
JPt100
-199.9 ... +500.0 °C
-199.9 ... +900.0 °F
Pt100
-200 ... +850 °C
-300 ... +1,500 °F
JPt100
-200 ... +500 °C
-300 ... +900 °F