WIKA operating instructions digital indicator, model DI25

14076218.01 12/2013 GB/D

GB

6. Commissioning, operation

Display

Name, function and setting range

Factory setting

Hysteresis alarm A1

Input of the hysteresis value for alarm A1

Setting range: 0.1 ... 100.0 or 1 ... 1,000 °C (°F)

Not available if no alarm type is selected for the alarm A1

1.0 °C

Hysteresis alarm A2

Input of the hysteresis value for alarm A2

Setting range: 0.1 ... 100.0 or 1 ... 1,000 °C (°F)

Not available when the option transmitter power supply [P24] is avail-

able or if no alarm type has been selected for alarm A2.

1.0 °C

Hysteresis alarm A3

Input of the hysteresis value for alarm A3

Setting range: 0.1 ... 100.0 or 1 ... 1,000 °C (°F)

Not available if no alarm type is selected for the alarm A3 or if the

high/low alarm was selected.

1.0 °C

Delay time alarm A 1

Input of the delay time for alarm A1

The alarm output is not switched until the set time after the alarm

value has been reached.

Setting range: 0 ... 9,999 seconds

Not available if no alarm type is selected for the alarm A1

0 seconds

Delay time alarm 2

Input of the delay time for alarm A2

The alarm output is not switched until the set time after the alarm

value has been reached.

Setting range: 0 ... 9,999 seconds

Not available when the option transmitter power supply [P24] is avail-

able or if no alarm type has been selected for alarm A2.

0 seconds

Delay time alarm 3

Input of the delay time for alarm A3

The alarm output is not switched until the set time after the alarm

value has been reached.

Setting range: 0 ... 9,999 seconds

Not available if no alarm type is selected for the alarm A3 or if the

high/low alarm was selected.

0 seconds

End value analogue actual-value output signal

Entering the displayed value, where the maximum value ( e.g. 20 mA)

of the analogue actual-value output signal is shown.

Setting range: Start value analogue actual-value output signal to

scaled end value.

1,370 °C

Start value analogue actual-value output signal

Entering the displayed value, where the minimum value ( e.g. 4 mA)

of the analogue actual-value output signal is shown.

Setting range: Scaled start value to end value analogue actual-value

output signal.

-200 °C