Gb 6. commissioning, operation – WIKA DI25 Benutzerhandbuch
Seite 23

23
WIKA operating instructions digital indicator, model DI25
14076218.01 12/2013 GB/D
GB
6. Commissioning, operation
Display
Name, function and setting range
Factory setting
Hysteresis alarm A1
■
Input of the hysteresis value for alarm A1
■
Setting range: 0.1 ... 100.0 or 1 ... 1,000 °C (°F)
■
Not available if no alarm type is selected for the alarm A1
1.0 °C
Hysteresis alarm A2
■
Input of the hysteresis value for alarm A2
■
Setting range: 0.1 ... 100.0 or 1 ... 1,000 °C (°F)
■
Not available when the option transmitter power supply [P24] is avail-
able or if no alarm type has been selected for alarm A2.
1.0 °C
Hysteresis alarm A3
■
Input of the hysteresis value for alarm A3
■
Setting range: 0.1 ... 100.0 or 1 ... 1,000 °C (°F)
■
Not available if no alarm type is selected for the alarm A3 or if the
high/low alarm was selected.
1.0 °C
Delay time alarm A 1
■
Input of the delay time for alarm A1
■
The alarm output is not switched until the set time after the alarm
value has been reached.
■
Setting range: 0 ... 9,999 seconds
■
Not available if no alarm type is selected for the alarm A1
0 seconds
Delay time alarm 2
■
Input of the delay time for alarm A2
■
The alarm output is not switched until the set time after the alarm
value has been reached.
■
Setting range: 0 ... 9,999 seconds
■
Not available when the option transmitter power supply [P24] is avail-
able or if no alarm type has been selected for alarm A2.
0 seconds
Delay time alarm 3
■
Input of the delay time for alarm A3
■
The alarm output is not switched until the set time after the alarm
value has been reached.
■
Setting range: 0 ... 9,999 seconds
■
Not available if no alarm type is selected for the alarm A3 or if the
high/low alarm was selected.
0 seconds
End value analogue actual-value output signal
■
Entering the displayed value, where the maximum value ( e.g. 20 mA)
of the analogue actual-value output signal is shown.
■
Setting range: Start value analogue actual-value output signal to
scaled end value.
1,370 °C
Start value analogue actual-value output signal
■
Entering the displayed value, where the minimum value ( e.g. 4 mA)
of the analogue actual-value output signal is shown.
■
Setting range: Scaled start value to end value analogue actual-value
output signal.
-200 °C