WIKA operating instructions digital indicator, model DI25

14076218.01 12/2013 GB/D

GB

3. Specifications

Accuracy
Current signal:

±0.2 % of measuring range ±1 digit

Voltage signal:

±0.2 % of measuring range ±1 digit

Thermocouples:

±0.2 % of measuring range ±1 digit or ±2 °C (4 °F), greater

value applies

Type R, S in the range 0 ... 200 °C (400 °F): ±6 °C (12 °F)

Type B in the range 0 ... 300 °C (600 °F): accuracy not

guaranteed.

Type K, J, E, T, N below 0 °C (32 °F): ±0.4 % of measur-

ing range ±1 digit

Resistance thermometers: ±0.1 % of measuring range ±1 digit or ±1 °C (2 °F), greater

value applies

Measuring rate:

4 measurements per second (measuring time 0.25 seconds)

Input
Thermocouples:

K, J, R, S, B, E, T, N, PL-II, C (W/Re5-26):

Permissible external resistance: max. 100 Ω

(Type B: max. 40 Ω)

Resistance thermometers: Pt100, JPt100, 3-wire

Wire resistance max. 10 Ω per wire

Current input:

0 ... 20 mA, 4 ... 20 mA

Input impedance: 50 Ω (external measurement shunt)

Permissible input current: max. 50 mA

Voltage input:

DC 0 ... 1 V

Input impedance: min. 1 MΩ

Permissible input voltage: max. DC 5 V

Permissible resistance of signal source: max. 2 kΩ

DC 0 ... 5 V, DC 1 ...5 V, DC 0 ... 10 V

Input impedance: min. 100 kΩ

Permissible input voltage: max. DC 15 V

Permissible resistance of signal source: max. 10 Ω