WIKA operating instructions digital indicator, model DI25

14076218.01 12/2013 GB/D

GB

6. Commissioning, operation

Current and voltage signals

4 ... 20 mA

-1999 ... 9999

With the input configuration 4 ... 20 mA or 0 ...

20 mA, the included 50 Ω measurement shunt

must be connected to the terminals 18 and 19.

0 ... 20 mA

-1999 ... 9999

DC 0 ... 1 V

-1999 ... 9999

DC 0 ... 5 V

-1999 ... 9999

DC 1 ... 5 V

-1999 ... 9999

DC 0 ... 10 V

-1999 ... 9999

6.4.3 Indication of alarm value

For display of the set alarm values during operation, press △ key and additionally the

MODE key. To display the next set alarm value, press the △ key again and additionally

the MODE key.

Name, function and setting range

Factory setting

Alarm value alarm 1 (A1)

■

The alarm value of the alarm A1 is indicated on the SV display and the A1 indicator

flashes.

■

Not available if no alarm type is selected for the alarm A1.

0 °C

Alarm value alarm 2 (A2)

■

The alarm value of the alarm A2 is indicated on the SV display and the A2 indicator

flashes.

■

Not available when the option transmitter power supply [P24] is available or if no alarm

type has been selected for alarm A2.

0 °C

Alarm value alarm 3 (A3)

■

The alarm value of the alarm A3 is indicated on the SV display and the A3 indicator

flashes.

■

Not available if no alarm type is selected for the alarm A3 or if the high/low alarm was

selected.

0 °C

6.5 Switch behaviour of the alarms

Switch behaviour activated (open-circuit principle, no, normally open)

While the display A1 (A2, A3) is ON (flashing), the alarm output of A1 (A2, A3) between

the connection terminals 7 - 8 (9 - 10, 12 - 13) is ON (relay activated).

The alarm output A1 (A2, A3) is OFF (relay deactivated) if the display of A1 (A2, A3) is

OFF (not flashing)

Switch behaviour deactivated (closed-circuit principle, nc, normally closed)

While the display A1 (A2, A3) is ON (flashing), the alarm output of A1 (A2, A3) between

the connection terminals 7 - 8 (9 - 10,12 - 13) is OFF (relay deactivated).