Gb 6. commissioning, operation – WIKA DI25 Benutzerhandbuch

Seite 25

Advertising
background image

25

WIKA operating instructions digital indicator, model DI25

14076218.01 12/2013 GB/D

GB

6. Commissioning, operation

6.4.1 Auxiliary parameter level 1

In order to configure the auxiliary parameter level 1, first press the ▽ key and additionally

the MODE key for 3 seconds. To switch to the next parameter, press the MODE key once

agian. After setting up the final parameter, exit the menu by pressing the MODE key.

Display

Name, function and setting range

Factory setting

Locking level

Prevents adjustments of parameters. Which parameters are locked

depends on the locking level selected:

(unlocked):

All parameters can be adjusted.

(Locking level 1): No parameters can be adjusted.

(Locking level 2): Only the alarm values can be adjusted.

(Locking level 3): All parameters can be adjusted. However,

the settings of the auxiliary parameter

level 2 are not permanently saved in the

instrument.

After switching off the power supply,

the old settings are reactivated once

switched on again.

Locking level 3 should be activated when operating with a serial interface

to prevent a constant overwriting of the EEProm

unlocked

Sensor correction

Input of the value for sensor correction.

Setting range: -100.0 ... +100.0 or -1,000 ... -1,000 °C (°F)

Corrects the input signal of the connected sensor. If the sensor cannot

be placed where a control is to be carried out, the measured temperature

can deviate from the temperature to be controlled. With the help of sensor

correction, an alignment can be made. Furthermore, it is possible to

compensate for deviations in the temperature sensor, which are detected

during a calibration.

0.0 °C

Transmission protocol

Selection of the transmission protocol.
WIKA protocol:

Modbus ASCII:

Modbus RTU:

Available only if the serial interface [C5] option is available.

WIKA protocol

Instrument address

Entering the individual instrument address for serial communication

with multiple instruments.

Setting range: 0 ... 95

Available only if the serial interface [C5] option is available.

0