Ein aus alarmwert hysterese, Gb 6. commissioning, operation – WIKA DI25 Benutzerhandbuch
Seite 30

30
WIKA operating instructions digital indicator, model DI25
14076218.01 12/2013 GB/D
GB
6. Commissioning, operation
The alarm output 1 is connected to the connection terminals 7 and 8, the alarm output 2
with the connection terminals 9 and 10 and the alarm output 3 with the connection termi-
nals 12 and 13.
High/low alarm (only for A3)
High alarm
Alarm behaviour
EIN
AUS
A2 (A1)
Alarmwert
[Hochalarm]
A2 (A1) Hysterese
A2 (A1)
Hysterese
EIN
AUS
[Tiefalarm]
A1 (A2) Hysterese
A1 (A2)
Hysterese
A1 (A2)
Alarmwert
EIN
AUS
[Hoch-/Tiefalarm]
A3
Schaltverhalten
[Low alarm]
A1 (A2) hysteresis
A1 (A2)
Alarm value
ON
OFF
[High alarm]
A2 (A1) hysteresis
A2 (A1)
Alarm
value
A1 (A2)
Hyster
esis
A2 (A1)
Hysteresis
[High/low alarm]
A3
Switch behaviour
ON
OFF
ON
OFF
Alarm output
EIN
AUS
A2 (A1)
Alarmwert
[Hochalarm]
A2 (A1) Hysterese
A2 (A1)
Hysterese
EIN
AUS
[Tiefalarm]
A1 (A2) Hysterese
A1 (A2)
Hysterese
A1 (A2)
Alarmwert
EIN
AUS
[Hoch-/Tiefalarm]
A3
Schaltverhalten
Alarm output OFF
Alarm output on
EIN
AUS
Alarmwert
Hysterese
Alarm output ON or OFF
The switch behaviour of the A3 high/low alarm depends on the switch behaviour of
alarm A1 and A2 (if A1 and A2 are OFF at the same time, A3 is ON). Therefore use the
standby function, hysteresis and time delay of alarm A1 and A2 with the utmost caution.
■
If the alarms A1 and A2 are in the standby mode, alarm A3 is ON.
■
If the hysteresis of A1 or A2 is increased, than the span for A3 ON is
decreases.
■
If the delay time of A1 or A2 is changed, the time for A3 also changes.
■
If the delay time for A1 or A2 is set and the delay of A1 or A2 is active,
than A3 is ON.