6. Commissioning, operation

The alarm output 1 is connected to the connection terminals 7 and 8, the alarm output 2

with the connection terminals 9 and 10 and the alarm output 3 with the connection termi-

nals 12 and 13.

High/low alarm (only for A3)

High alarm

Alarm behaviour

EIN

AUS

A2 (A1)

Alarmwert

[Hochalarm]

A2 (A1) Hysterese

A2 (A1)

Hysterese

EIN

AUS

[Tiefalarm]

A1 (A2) Hysterese

A1 (A2)

Hysterese

A1 (A2)

Alarmwert

EIN

AUS

[Hoch-/Tiefalarm]

A3

Schaltverhalten

[Low alarm]

A1 (A2) hysteresis

A1 (A2)

Alarm value

ON

OFF

[High alarm]

A2 (A1) hysteresis

A2 (A1)

Alarm

value

A1 (A2)

Hyster

esis

A2 (A1)

Hysteresis

[High/low alarm]

A3

Switch behaviour

ON

OFF

ON

OFF

Alarm output

EIN

AUS

A2 (A1)

Alarmwert

[Hochalarm]

A2 (A1) Hysterese

A2 (A1)

Hysterese

EIN

AUS

[Tiefalarm]

A1 (A2) Hysterese

A1 (A2)

Hysterese

A1 (A2)

Alarmwert

EIN

AUS

[Hoch-/Tiefalarm]

A3

Schaltverhalten

Alarm output OFF

Alarm output on

EIN

AUS

Alarmwert

Hysterese

Alarm output ON or OFF

The switch behaviour of the A3 high/low alarm depends on the switch behaviour of

alarm A1 and A2 (if A1 and A2 are OFF at the same time, A3 is ON). Therefore use the

standby function, hysteresis and time delay of alarm A1 and A2 with the utmost caution.

If the alarms A1 and A2 are in the standby mode, alarm A3 is ON.

If the hysteresis of A1 or A2 is increased, than the span for A3 ON is

decreases.

If the delay time of A1 or A2 is changed, the time for A3 also changes.

If the delay time for A1 or A2 is set and the delay of A1 or A2 is active,

than A3 is ON.