DIGITAL INDUSTRIAL CONTROLLER
english
The following output configurations are available:
Controller output for continuous signals
•
Output for standard signal 0 ... 10 V
Terminals 33 and 34
max. load current:
5 mA
Accuracy:
0,5 %
•
Output for standard signal 0 (4) ... 20 mA
Terminals 32 and 33
max. load resistance:
600
Ω
Accuracy:
0,5 %
Controller outputs for discontinuous signals
2 relays with one potential free changeover contact each:
Relay 1
Terminals 7, 8 and 9
Relay 2
Terminals 10, 11 and 12
4.4
Signal outputs
Controller output
•
Input for the connection of a potentiometer
Terminals 19, 20 and 27
for position feedback (1 ... 10 k
Ω)
for position regulation
•
Binary inputs
Terminals 25 and 26
Input resistance:
> 25 k
Ω
Configurable line of action:
Logical value
Voltage
not inverted
inverted
0
0 ... 4,5 V
nactive
active
1
13 ... 35 V
active
inactive
Configurable functions:
•
Changeover between manual and automatic mode
•
Changeover between external and internal setpoint *)
•
Triggering alarms
•
Safety value output
*) Available only if controller input 2 has been configured for an external setpoint.