1110 - 55
DIGITAL INDUSTRIAL CONTROLLER
english
Cascade control
Manipulated variable limiting (main controller)
COh:
High manipulated variable limit
Adjustment limit: COl
≤ COh ≤ 100 (in %)
COl:
Low manipulated variable limit
Adjustment limit: 0
≤ COl ≤ COh (in %)
Direction of action (Main controller)
Inv: no
The main controller (PID controller 1) works with positive direction of
action
Inv: yes
The main controller (PID controller 1) works with negative direction of
action
Sub-menus of the main menu option
INPUT 1 (controller input 1)
Signal type
Frequency
Input for a frequency-analog signal
0...10 V
Input for 0..10 V standard signal
0...20 mA
Input for 0..20 mA standard signal
4...20 mA
Input for 4..20 mA standard signal
Pt 100
Input for connection of Pt 100 resistance thermometers
TC type J
TC type K
TC type T
Input for connection of thermocouples
TC type R
TC type S
Root extraction
This function is only offered when using standard signals.
√
: off
Root extraction function off
√
: on
Root extraction function on
Pt100 Connection
Mode of connection of the Pt 100 sensor
Pt100 : 3
Pt 100 sensor is connected by 3 wires (3-wire technique)
Pt100 : 4
Pt 100 sensor is connected by 4 wires (4-wire technique)
If a 3-wire connection is selected the terminals 35 and 36 have to be shorted by a
wire (see connection allocation)