English, Digital industrial controller, 2 supply voltages – Burkert Type 1110 Benutzerhandbuch
Seite 9

1110 - 7
DIGITAL INDUSTRIAL CONTROLLER
english
Fig. 3: Allocation of the terminal strip
4.2
Supply voltages
ATTENTION!
To ensure the electro-magnetic compatibility (EMC), the screw
terminal TE (Technical Earth) must be connected to the earth
potential with a short cable (30 cm, 2.5 mm
2
).
NOTE
When connecting the sensor lines:
•
Lay the lines separate from the power lines (lines in which large
currents flow) and high frequency lines. Never under any
circumstances use multi-pole cables to carry both power and
sensor lines.
•
When using screened cables, only connect the screen at one
end. Never under any circumstances connect the screen to both
the protective conductor and the earth of the regulator input.
Power supply for the
Connect to terminals 14
controller:
and 15.
Model 1:
115 / 230V 50 ... 60 Hz
Model 2:
12 / 24V 50 ... 60 Hz
Power supply for
24 V DC
Accessible on terminals 23
transducers:
and 24.
Resistance
thermometer
PT100
Relay 3
(Alarm)
Relay 3
(Alarm)
Relay 1
(Output)
Relay 2
(Output)
Power
supply
Binary
input
Binary
output
Position acknow-
ledgement
Controller input 2
Controller input 1
Controller output
Standard signal
Current
Standard signal
Voltage
Thermo
couples