DIGITAL INDUSTRIAL CONTROLLER
english
Function block 19:
3-point step signal with external position
acknowledgement (Position control)
This signal serves to control motor-driven actuators on which a position
acknowledgement is provided by way of a potentiometer. The resistance value of the
acknowledgement potentiometer must be within the range from 1 k
Ω to 10 kΩ.
Adjustable parameters:
Psh:
Switching hysteresis
Psd:
Insensitivity zone
Figure 21: 3-point step signal
Function block 20: PID controller 1
This function block is a parameter-definable PID controller that is used as a main
controller for cascade control.
Adjustable parameters:
Kp:
Proportional action coefficient / Gain
Tr:
Reset time
Td:
Derivative action time
Pdb:
Dead area
CO0:
Operating point
Relay output
Psh
Psd
SP
PV