English, Digital industrial controller, 8error messages and warnings – Burkert Type 1110 Benutzerhandbuch
Seite 83

1110 - 81
DIGITAL INDUSTRIAL CONTROLLER
english
The Digital Controller carries out a self-test each time it is switched on. The data
memory, the program memory and the non-volatile memory are checked during the
course of the self test.
Correct functioning of the inputs and outputs can also be tested during operation. If
an error occurs, it is displayed in the second line of the display. The error display
does not disappear until the error has been remedied.
The controller assumes the MANUAL mode whenever an error occurs.
Error mesages during the self test:
8
ERROR MESSAGES AND WARNINGS
Error message
Cause
Controller status
Remedy
Para defective
The parameterisation
The controller
Parameterise the
data stored in the
switches to MANUAL
controller again
EEPROM is
mode and remains
(see Parameterisa-
defective.
the self-test phase.
tion.)
Config defetive
The configuration
The controller
Configure the con-
data stored in the
switches to MANUAL
troller again (see
EEPROM is
mode and remains
Configuration)
defective.
the self-test phase.
SP def
The status data
The controller
Set the setpoint
stored in the
switches to MANUAL
again and then
EEPROM is
mode.
switch the controller
defective.
to AUTO mode.
KalDef
The calibration
The controller
This fault cannot
data stored in the
assumes the status
be remedied by
EEPROM is
it was in before
the user.
defective.
switching off. The
controller operates
with limited accuracy.