English, Digital industrial controller, 3 signal inputs – Burkert Type 1110 Benutzerhandbuch

Seite 11

Advertising
background image

1110 - 9

DIGITAL INDUSTRIAL CONTROLLER

english

All signal inputs are short-circuit proof, are voltage-stable to 41 volts and are
galvanically isolated with regard to the outputs and the supply voltage.

Controller input 1:

The following input configurations are available:

• Input for standard signal (voltage) 0 ... 10 V

Terminals 30 and 31

Input resistance:

> 400 k

Measuring error:

< 0,2 %

Temperature influence:

< 0.2 % / 10 degrees

Input for standard signal (current) 0 (4) ... 20 mA

Terminals 29 and 31

Input resistance:

< 300

Ω in accordance with DIN IEC 381 (typically 200)

Measuring error:

< 0,2 %

Temperature influence:

< 0.2 % / 10 degrees

Nominal temperature:

22 °C

Wire breakage and short-circuit detection within the range from 4 to 20 mA

• Input for frequency-analog signal 5 ... 1000 Hz

Terminals 28 and 31

Input resistance:

> 10 k

Measuring error:

< 0,1 %

Signal types:

Sine wave, square wave, delta ( > 300 mVpp)

4.3

Signal inputs

Input for connection of Pt 100 resistance

Terminals 35, 36, 37, 38

thermometers
(in accordance with DIN 43760 for 3 and 4-wire connection)

Measurement range

- 200 to + 850 °C

Measurement current

max. 0,5 mA

Measuring error

± 0.2 % ± 2 digits