Function block 19:

3-point step signal with external position
acknowledgement (Position control)

This signal serves to control motor-driven actuators on which a position
acknowledgement is provided by way of a potentiometer. The resistance value of the
acknowledgement potentiometer must be within the range from 1 k

Ω to 10 kΩ.

Adjustable parameters:

Psh:

Switching hysteresis

Psd:

Insensitivity zone

Figure 21: 3-point step signal

Function block 20: PID controller 1

This function block is a parameter-definable PID controller that is used as a main
controller for cascade control.

Adjustable parameters:

Kp:

Proportional action coefficient / Gain

Tr:

Reset time

Td:

Derivative action time

Pdb:

Dead area

CO0:

Operating point