DIGITAL INDUSTRIAL CONTROLLER

english

Function block 9: Alarm, relative

This function actuates the alarm relays when the system deviation exceeds a high
limit or falls below a low limit. In this case, therefore, the limits are referred to the
setpoint (relative). This alarm function is not available when ratio control is
configured.

High limit violation:

Alarm via relay 3

Low limit violation:

Alarm via relay 4

Adjustable parameters:

PV+ :

High alarm limit

PV- :

Low alarm limit

Hy :

Switching hysteresis

Function block 10: PID controller (2)

This function block is a parameter-definable PID controller that can be used either
as a single controller or as an auxiliary controller within the scope of cascade
control.

Adjustable parameters:

Kp:

Amplification factor

Tr:

Reset time

Td:

Derivative action time

CO0:

Operating point

Function block 11: Line of action

Here, a function selector can be used to set whether the actuator is to be triggered
with a positive or negative line of action. When a positive line of action is set, the
output signal CO of PID controller 2 increases along with rises in the system
deviation PVd, while it decreases when the line of action is negative.

Options:

Inv. no: positive line of action

Inv. yes:negative line of action