English, Digital industrial controller – Burkert Type 1110 Benutzerhandbuch

Seite 68

Advertising
background image

66 - 1110

DIGITAL INDUSTRIAL CONTROLLER

english

BinOut

Definition of the binary output’s function

none

Not active

Alarm

Output active when an alarm occurs

man/auto

Output active in MANUAL mode

Error

Output active if one of the following errors occurs:

Input error

Output error

Internal error

Ramp

Definition of the parameters for the setpoint ramp

off:

Setpoint ramp not active

on:

Setpoint ramp active. An entered setpoint is moved to via the
setpoint ramp.

D:

Setpoint ramp pitch
Adjustment range:

0

≤ D ≤ 999

(Setpoint change per minute)

The setpoint ramp and the Tune or Adaption function (in the case of cascade control;
adaption of the main controller) cannot be executed simultaneously. If the ramp
function is activated in the configuration or parametrisation level, Tune and Adaption
are deactivated automatically in the AdapReg or AdapReg 1 menus. Conversely,
activating Tune or Adaption in the configuration or parametrisation level deactivates
the ramp function. The function activated last (Tune or Adaption or ramp) therefore
has priority.

SP track

Definition of the parameters for setpoint tracking

SPT: off

Setpoint tracking not in operation

SPT: on

Setpoint tracking is on
(Jolt-free changeover between MANUAL and AUTOMATIC mode)

S:

Pitch of the setpoint tracking ramp
Adjustment range:

0

≤ S ≤ 9999

(Setpoint change per minute)