1110 - 61

DIGITAL INDUSTRIAL CONTROLLER

english

2-point PWM

(2-point PWM signal)

Period

T+:

Period of the PWM signal
(refers to relay 1)
Adjustment range:

1

≤ T+ ≤ 999,9 (in sec.)

Manipulated variable limiting

COh:

High manipulated variable limit
Adjustment range:

COl

≤ COh ≤ 100 (in %, with reference to

the time period of the PWM Output T+)

COl:

Low manipulated variable limit
Adjustment range:

0

≤ COl ≤ COh (in %, with reference to

the time period of the PWM Output T+)

The upper manipulated value limit determines the maximum switch-on time, and the
lower regulated value limit the minimum switch-on time of the Output Relay 1. The
entry of the switch-on time is made as a percentage of the time period.

Line of action

inv: no

The output operates with a positive line of action

inv: yes

The output operates with a negative line of action

Pulse output

This function allows you to trigger a pulse valve.
(Relay 1 controls the pickup winding, while relay 2 controls the dropout winding)

Imp: no

Pulse valve is not used

Imp: yes

Pulse valve is used

3-point PWM

(3-point PWM signal)

Period

T+:

Period of the PWM signal for „Heating“ (Relay 1)
Adjustment range:

1

≤ T+ ≤ 999.9 (in sec.)

T-:

Period of the PWM signal for „Cooling“ (Relay 1)
Adjustment range:

1

≤ T- ≤ 999.9 (in sec.)