English, Digital industrial controller – Burkert Type 1110 Benutzerhandbuch

Seite 82

Advertising
background image

80 - 1110

DIGITAL INDUSTRIAL CONTROLLER

english

Status displays

In the operator control mode, the

Adap or Tune status message flashes every 5 sec

in the second line of the display whenever an adaption or tune cycle is
running.
Specific statuses and controller settings may lead to a situation in which an adaption
cycle cannot be started. The reason for this is indicated by the

not ready status

message and by a two-digit code displayed for 5 sec. Refer to the following table for
the meanings of the codes.

Code

Meaning

01

External setpoint input active

02

Setpoint tracking active

03

Setpoint ramp active

04

Measured variable in a non-stationary state

05

Main controller not in MANUAL mode (cascade control only)

06

Subordinate controller not in Automatic mode (cascade control only)

07

Resolution less than minimum (setpoint change too small)

Advertising