The Digital Controller carries out a self-test each time it is switched on. The data
memory, the program memory and the non-volatile memory are checked during the
course of the self test.
Correct functioning of the inputs and outputs can also be tested during operation. If
an error occurs, it is displayed in the second line of the display. The error display
does not disappear until the error has been remedied.
The controller assumes the MANUAL mode whenever an error occurs.

Error mesages during the self test:

8

ERROR MESSAGES AND WARNINGS

Error message

Cause

Controller status

Remedy

Para defective

The parameterisation

The controller

Parameterise the

data stored in the

switches to MANUAL

controller again

EEPROM is

mode and remains

(see Parameterisa-

defective.

the self-test phase.

tion.)

Config defetive

The configuration

The controller

Configure the con-

data stored in the

switches to MANUAL

troller again (see

EEPROM is

mode and remains

Configuration)

defective.

the self-test phase.

SP def

The status data

The controller

Set the setpoint

stored in the

switches to MANUAL

again and then

EEPROM is

mode.

switch the controller

defective.

to AUTO mode.

KalDef

The calibration

The controller

This fault cannot

data stored in the

assumes the status

be remedied by

EEPROM is

it was in before

the user.

defective.

switching off. The
controller operates
with limited accuracy.