1110 - 55

DIGITAL INDUSTRIAL CONTROLLER

english

Cascade control

Manipulated variable limiting (main controller)

COh:

High manipulated variable limit
Adjustment limit: COl

≤ COh ≤ 100 (in %)

COl:

Low manipulated variable limit
Adjustment limit: 0

≤ COl ≤ COh (in %)

Direction of action (Main controller)

Inv: no

The main controller (PID controller 1) works with positive direction of
action

Inv: yes

The main controller (PID controller 1) works with negative direction of
action

Sub-menus of the main menu option

INPUT 1 (controller input 1)

Signal type

Frequency

Input for a frequency-analog signal

0...10 V

Input for 0..10 V standard signal

0...20 mA

Input for 0..20 mA standard signal

4...20 mA

Input for 4..20 mA standard signal

Pt 100

Input for connection of Pt 100 resistance thermometers

TC type J
TC type K
TC type T

Input for connection of thermocouples

TC type R
TC type S

Root extraction

This function is only offered when using standard signals.

: off

Root extraction function off

: on

Root extraction function on

Pt100 Connection

Mode of connection of the Pt 100 sensor

Pt100 : 3

Pt 100 sensor is connected by 3 wires (3-wire technique)

Pt100 : 4

Pt 100 sensor is connected by 4 wires (4-wire technique)

If a 3-wire connection is selected the terminals 35 and 36 have to be shorted by a
wire (see connection allocation)