English, Digital industrial controller – Burkert Type 1110 Benutzerhandbuch

Seite 80

Advertising
background image

78 - 1110

DIGITAL INDUSTRIAL CONTROLLER

english

Accordingly, several adaption cycles are run until the required setpoint is reached,
thus increasing the quality of the controller parameters. A new setpoint is set in up to
5 stages. However, only as many steps are run through as are needed to find the
optimum controller parameters.

Depending on the scaling range of the controller input (PVl ... PVh / P2l ... P2h), the
setpoint change must exceed a specific amount for adaption to take place. In the
following table you find the minimum set point changes to execute in dependence of
the configured controller inputs 1 and 2. The data applies to activation of a setpoint
in one stage.

Configured controller input

minimum setpoint change to execute

Standard signal 0 … 10 V

(PVh - PVl) • 0,0135

Standard signal 0 … 20 mA

(PVh - PVl) • 0,0135

Standard signal 4 … 20 mA

(PVh - PVl) • 0,0169

Frequency-analog signal

(PVh - PVlu) • 0,0153

Pt 100 (-200 … + 850 °C)

20,0 K

Thermocouple type J (-200 … 1200 °C)

16,5 K

Thermocouple type K (-200 … 1370 °C)

28,0 K

Thermocouple type T (0 … 400 °C)

16,5 K

Thermocouple type R (0 … 1760 °C)

50,0 K

Thermocouple type S (0 … 1760 °C)

50.0 K

note: P*h: PVh oder P2h; P*l: PVl oder P2l.

If the setpoint change is too less this status is displayed by the code 07 (see Par.
7.6).

Handling adaption if you have an inadequate knowledge of the process

If you have an inadequate knowledge of the process (time response and gain etc.)
when commissioning a control system, you are advised to proceed as follows when
using the self-optimisation function by adaption:

Advertising