30 - 1110

DIGITAL INDUSTRIAL CONTROLLER

english

Figure 17: Line of action with reference to the P controller

Functional block 12:

Setting the regulated variables

This function block can be used to define the range within which the controlled
variable CO may vary.

Adjustable parameters:

COh:

Maximum value of the controlled variable

COl:

Minimum value of the controlled variable

For 3-point PWM signals, the heating / cooling range can be limited separately. If the
variable is at a limit value, the integrator circuit will be active.

Chh:

Maximum value of the heating variable (Relay 1)

Chl:

Minimum value of the heating variable (Relay 1)

Cch:

Maximum value of the cooling variable (Relay 2)

Ccl:

Minimum value of the cooling variable (Relay 2)

For a 3-point step output without external feedback, the variable limitation is not
available.

Function block 13: Safety value

Here, you specify the controlled variable that is to be output in the event of a
malfunction occurring or if the binary input is activated (when the „Output safety
value“ function is configured; see Section 6.5.4)

Adjustable parameters:

COs:

Safety value of the control variable

positiver Wirkungssinn

negativer Wirkungssinn

xd (Regeldifferenz)

Y

0

Negative line of action

PVd (system deviation)

Positive line of action

CO