English, Digital industrial controller, 4 signal outputs – Burkert Type 1110 Benutzerhandbuch

Seite 13

Advertising
background image

1110 - 11

DIGITAL INDUSTRIAL CONTROLLER

english

The following output configurations are available:

Controller output for continuous signals

Output for standard signal 0 ... 10 V

Terminals 33 and 34

max. load current:

5 mA

Accuracy:

0,5 %

Output for standard signal 0 (4) ... 20 mA

Terminals 32 and 33

max. load resistance:

600

Accuracy:

0,5 %

Controller outputs for discontinuous signals

2 relays with one potential free changeover contact each:

Relay 1

Terminals 7, 8 and 9

Relay 2

Terminals 10, 11 and 12

4.4

Signal outputs

Controller output

Input for the connection of a potentiometer

Terminals 19, 20 and 27

for position feedback (1 ... 10 k

Ω)

for position regulation

Binary inputs

Terminals 25 and 26

Input resistance:

> 25 k

Configurable line of action:

Logical value

Voltage

not inverted

inverted

0

0 ... 4,5 V

nactive

active

1

13 ... 35 V

active

inactive

Configurable functions:

Changeover between manual and automatic mode

Changeover between external and internal setpoint *)

Triggering alarms

Safety value output

*) Available only if controller input 2 has been configured for an external setpoint.