DIGITAL INDUSTRIAL CONTROLLER

english

Overlap area

When using the 3-point PWM Output, the following controller behaviour results in
the area around the set-point, depending on the setting of the overlap area:

Figure 20:

Overlap area for 3-point PWM signal

Adjustable parameters:

T+:

Period for switching relay 1 (heating)

T-:

Period for switching relay 2 (cooling)

Olp:

Overlap zone (heating and cooling)

Funktionsblock 18: 3-Punkt-Schritt-Signal

The 3-point step signal can be used to control motor-driven actuators. In doing so,
TCO is the time needed to move the actuator from one end position to the other.

Adjustable parameters:

Gt:

Backlash of the gearbox when shifting from forwards to reverse

Psd:

insensitive area (for explanation, refer to Chapter 6.5.4)

TCO:

Regulating time (motor running time)

Overlap area negative
(Dead range)

OLP < 0

Setpoint SP

Actual value PV

Heat

Cool

100 %

Controlled

variable CO

Characteristic

for P-controller

OLP > 0

Setpoint SP

Actual value PV

Heat

Cool

100 %

Controlled

variable CO

Characteristic

for P-controller

Overlap area positive
(overlap)