English, Digital industrial controller, 2 supply voltages – Burkert Type 1110 Benutzerhandbuch

Seite 9

Advertising
background image

1110 - 7

DIGITAL INDUSTRIAL CONTROLLER

english

Fig. 3: Allocation of the terminal strip

4.2

Supply voltages

ATTENTION!

To ensure the electro-magnetic compatibility (EMC), the screw
terminal TE (Technical Earth) must be connected to the earth
potential with a short cable (30 cm, 2.5 mm

2

).

NOTE

When connecting the sensor lines:

Lay the lines separate from the power lines (lines in which large
currents flow) and high frequency lines. Never under any
circumstances use multi-pole cables to carry both power and
sensor lines.

When using screened cables, only connect the screen at one
end. Never under any circumstances connect the screen to both
the protective conductor and the earth of the regulator input.

Power supply for the

Connect to terminals 14

controller:

and 15.

Model 1:

115 / 230V 50 ... 60 Hz

Model 2:

12 / 24V 50 ... 60 Hz

Power supply for

24 V DC

Accessible on terminals 23

transducers:

and 24.

Resistance
thermometer
PT100

Relay 3
(Alarm)

Relay 3
(Alarm)

Relay 1
(Output)

Relay 2
(Output)

Power

supply

Binary
input

Binary
output

Position acknow-
ledgement

Controller input 2

Controller input 1

Controller output

Standard signal
Current

Standard signal
Voltage

Thermo
couples