DIGITAL INDUSTRIAL CONTROLLER

english

Error message

In1Err

1)

In2Err

2)

OutErr

NTCErr

Cause

An error has been
detected at the first
controller input.

An error has been
detected at the 2nd
controller input.

An error has been
detected at the
controller output.

A defect has been
detected on the
temperature sensor
for internal compa-
rison.

Controller status

Controller switches to
MANUAL mode.

Controller switches to
the MANUAL mode.

Controller switches to
the MANUAL mode.

The controller remains
in the state it was in
before the error
occurred. A constant
point compensation
temperature of 20 °C
is set as the
temperature for the
comparison point

Remedy

Check and repair the
connected sensor
and wiring. The
controller remains in
MANUAL mode and
may have to be
switched back to
AUTO mode by way
of the keyboard.

Check and repair the
connected sensor
and wiring. The
controller remains in
MANUAL mode and
may have to be
switched back to
AUTO mode by way
of the keyboard.

Check and repair the
connected actuator
and wiring. The
controller remains in
MANUAL mode and
may have to be
switched back to
AUTO mode by way
of the keyboard.

This error cannot be
remedied by the
user.

1)

An error at input 1 can only be detected when using the following sensor types:

Pt100, Thermocouples, standard signal inputs: 0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA

2)

An error at input 2 can only be detected when using the following sensor types:

Standard signal inputs: 0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA.