DIGITAL INDUSTRIAL CONTROLLER

english

Sub-menu of the main menu optional SAFETY (safety value)

COs:

Safety value for the manipulated variable.
This value is output if one of the following events occurs:
• Error at the input
• Internal error
• Binary input becomes active and is configured for output of the
safety value.
Adjustment range:

COl

≤ COs ≤ COh (in %)

For 3-point Output:

Ccl

≤ COs ≤ Cch or

Chl

≤ COs ≤ Chh (in %)

SUB-MENU of the main menu option

AdapCont

Tune

Function for self-optimisation of the controller parameters by self-adjustment (see
Section 7) when using an output for standard signals; 2-point PWM signals and 3-
point PWM
signals.

Tune: on

Self-adjustment takes place after a setpoint change.

Tune: off

The Tune function is not used.

Adaption

Function for self-optimisation of the controller parameters by adaption
(see Section 7) when using an output for standard signals and 3-point step signals.

Adapt: on

Adaption takes place after a setpoint change.

Adapt: off

Adaption is off.

Optimization steps

SP

↑↑: no

A newly entered setpoint is moved to in one step.

SP

↑↑: yes

A newly entered setpoint is moved to in several steps (up to 5 set-
point steps). The controller parameters are optimised in each step.

Transition response

PV

↑: no

Controller parameters are optimised to aperiodic transition res-
ponse, without overshoot of the control variable. This leads to a
correspondingly longer initial stabilisation time (cf. Section 7).

PV

↑: yes

Controller parameters are optimised to the shortest initial
stabilisation time with approx. 5% overshoot.