1110 - 65

DIGITAL INDUSTRIAL CONTROLLER

english

Sub-menus of the main menu option

OPTIONS

Language

Language definition

German

English

French

Serial

This menu point only appears if the RS 232, RS 485/Profibus cards are installed
(see Operating Instructions for the RS 232, RS 485 / Profibus serial interface cards).

BinIn

Definition of the binary input’s function

none

not in operation

Alarm

Alarm relay 1 is switched via the binary input.

man/auto

Changeover between MANUAL and AUTOMATIC takes place via
the binary input.

Safety

The safety value is output through the binary input. (The controller
switches to MANUAL mode.) The manipulated variable cannot be
adjusted in this mode.

ext/intW

Via the binary input, switching between the external set-point (set-
point which is given as an electrical signal via the 2nd
input) and the internal set-point (set point pre-defined via the unit
keyboard) is possible. This menu point is only available in the
“external set-point” controller structure.

Line of action

inv: no

non-inverted line of action

inv: yes

inverted line of action