D Important B2-standards

1 E-stop function according to DIN EN 13850

Requirements on the function

ƒ

It must always be available (4.1.1)

ƒ

It takes priority over all other commands (4.1.1)

ƒ

It must not affect the effectiveness of the safety

devices (4.1.2) ( possibly continuing operation of auxiliary

devices, e.g. breaks)

ƒ

It must not cause additional hazards (4.1.3)

(e.g. the rescue of persons must be possible)

ƒ

After the reset command, no activation

of restart command is allowed (4.1.6)

ƒ

It must avert danger in the best possible way.



2 Stop-function according to DIN EN 60204 part 1


There are the categories of stop-functions:

Category 0:

Shutdown by immediate breaking of the power to the machines
– drive sections.


Category 1:

A controlled shutdown whereas the power to the machines

– drive sections is maintained to break. The power will only be

interrupted if idleness has been reached.