F Applications of riese safety relays

Attention : Using external contactors in application spark quenching circuits are required and must be

connected directly to the contactor.

1 Product application

- emergency stop relay

-

safety gate monitoring relay

a) SAFE 1 / SAFE 1.1

(SAFE 1 : with start control)
(SAFE1.1: without start control)


Single channel emergency stop


By pressing the START button the unit is
activated. Contacts 13-14, 23-24, 33-34 close
and contact 41-42 opens. Pressing the
emergency stop will reset the contacts.

Suitable up to category 2; SIL1; PLd reachable

Single channel emergency stop with external

contact extension (1 contactor) and contact

monitoring.


This application uses one external positive guided
contactor. One normally closed contact of each
contactor must be connected in series to the
START button. Through the switch S ext. the
external contactor can be operated or turned off
at any time the SAFE 1 is activated.

Suitable up to category 2; SIL1; PLd reachable

Single channel safety gate monitoring.


If switch S1 of the safety gate is closed the output
contacts do not change state. Pressing the
START button activates the SAFE 1. When
contacts 13-14, 23-24 and 33-34 close and
contact 41-42 opens. Opening S1 of the safety
gate the reset immediately.

Suitable up to category 2; SIL1; PLd reachable

24V AC/DC

A2(-)

Y1

Y2

A1(+)

START

S1

41

13

33

23