application guide safety relays from riese electronic

page 63

Logical AND circuit of two devices.


After opening the e-stop circuits of the device

A,

the contactors K1/K2 de-energise. Because the
safety outputs of device

A have now a 0V-

potential and the device

B is configured for the

AND-combination (due to the open circuit S32),
the contactors K3/K4 will be de-energised over
the S33 terminal (AND combination) too. If only
the release switch of device

B will be opened,

the contactors K3/K4 will be de-energised only.
The contactors K1/K2 remains in energised
condition. Hence device

A de-energises all its

following devices.

up to category 4; SIL3; PLe reachable





Contact extension over the emergency stop

circles.


See also application 6:

Logical AND circuit of

two devices.

up to category 4; SIL3; PLe reachable