application guide safety relays from riese electronic

page 21

Safety gate applications SAFE 2 / 2.1


Single-channel safety gate monitoring.


If the button S1 of the safety gate is closed the
output contacts do not change. Pressing the
START-button activates the SAFE2. The
contacts 13-14,23-24 close.
After the opening of the protection door switch
the contacts return to their normal position
without delay.

up to category 2; SIL1; PLd reachable

Additional advice
With wiring according to application the user
must provide a connection to the machine control
for cyclic testing.


Dual-channel protection door monitoring with

opposite polarity between channels.


If the safety gate switches are closed, the output
contacts remain unchanged. After the release of
the unit, the contacts 13-14 and 23-24 close.
After opening the protection door switches the
contacts return to their normal position without
delay.

up to category 4; SIL3; PLe reachable




Dual-channel protection door monitoring with

automatic activation and with opposite

polarity between channels.

(only Safe 2.1)


For this application the unit SAFE 2.1 has to be
used. The activation works automatically, since
the terminals S33/S34 are bridged. If the
protection door switches close, the contacts 13-
14, 23-24 close. After the opening of the
protection door switches the contacts return to
their normal position without delay.

up to category 4; SIL3; PLe reachable

A1

S34

S33

S11 S12 S21 S22

A2

Start

+24V 0V

S1

S1

S2

A1

S34

S33

S11 S12

S21 S22

A2

+24V 0V

Freigabe /

release

S1

S2

A1

S34

S33

S11 S12

S21 S22

A2

+24V 0V