application guide safety relays from riese electronic

page 80

Combination examples

Logical AND circuit of two devices.

After opening the release switch circuits of device A, the contactors
K1/K2 de-energise. Because the safety outputs of device A have
now a 0V-potential and the device B is configured for the AND-
combination (due to the open circuit S32), the contactors K3/K4 will
be de-energised over the S33 terminal (AND combination) too. If
only the release switch of device B will be opened, the contactors
K3/K4 will be de-energised only. The contactors K1/K2 remains in
energised condition. Hence device A de-energises all its following
devices.

up to category 4; SIL3; PLe reachable

S32

S33

24

S11

K1

K2

K3

K4

14

A

B

24
14

safety
input

safety

input