NORSTAT Safety Relays Benutzerhandbuch

Seite 52

Advertising
background image

application guide safety relays from riese electronic

page 49

Dual channel emergency circuit with external

contact expansion (two contactors), contact

monitoring and opposite polarity between

channels.


In this application external contactors with
positive guided contacts are used. One normally
closed contact of each contactor must be
connected series to START button and between
the terminals T11 and T34. Contacts 13-14
close when the device is activated by pressing
the START button. The external contactors will
energize. Pressing the OFF or E-STOP button
the contacts of the SAFE S.8 / SAFE S.10 and
the external contactors return to their normal
position.
With the S ext. switch the external contactors
can be operated or turned OFF at any time if the
SAFE S.8 / SAFE S.10 is activated.

Suitable up to category 4; SIL3; PLe reachable



Single channel safety gate monitoring

Without opposite polarity between channels.


If the safety gate switch S1 is closed, the output
contacts remain unchanged. The device will be
activated by pressing the START button.
Contacts 13-14 and 23-24 close with a delay of
approximately 100 ms. Opening the safety gate
switch returns the contacts to their normal
position without delay.

Suitable up to category 2; SIL1; PLd reachable





Dual channel safety gate monitoring without

opposite polarity between channels.


If the safety gate switches S1 and S2 are closed,
the output contacts remain unchanged. The
device will be activated by pressing the Release
switch. Contacts 13-14 and 23-24 close with a
delay of approximately 100 ms. Opening the
safety gate switches returns the
contacts to their normal position without delay.

Suitable up to category 3; SIL2; PLd reachable


T12

T44/

Fr

ei

ga

be

T11 T34

PE

T22

S 1

23

T33

13

T33

S 2

PE

T44/

Freigabe /
Release

T11 T34

T22 T12

S 1

13

23

PE

Not-
Halt/
E-
STOP

T33

T34

T11

K2 ext.

S

TA

R

T

K1 ext.

13

T44/

Uext.

T12

T22

13

23

K2 ext.

K1 ext.

K

SAFE S...

14

Sext.

NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866

Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com