application guide safety relays from riese electronic

page 47

Y1

Y2

23

A2(-)

A1(+)

13

24V AC/DC

14

24

Start

Not-

STOP

E-

Halt/

Y1

Y2

23

A2(-)

A1(+)

13

24V AC/DC

14

24

K1

K2

K1

K2

Sext

Uext

Start

Not-

STOP

E-

Halt/

d) SAFE 5 / SAFE 5.1

(SAFE 5 : without start control)
(SAFE5.1: with start control)

Single channel emergency stop


By pressing the START button the unit is
activated. Contacts 13-14, 23-24, 33-34 close
and contact 41-42 opens. Pressing the
emergency stop will reset the contacts.

Suitable up to category 2; SIL1;PLd reachable

Single channel emergency stop with external

contact extension (1 contactor) and contact

monitoring.

This application uses one external positive
guided contactor. One normally closed contact
of each contactor must be connected in series to
the START button. Through the switch S ext. the
external contactor can be operated or turned off
at any time the SAFE 5.1 is activated .

Suitable up to category 2; SIL1;PLd reachable

Single channel safety gate monitoring.


If switch S1 of the safety gate is closed the
output contacts do not change state. Pressing
the START button activates the SAFE 5.1.
When contacts 13-14, 23-24 and 33-34 close
and contact 41-42 opens. Opening S1 of the
safety gate the reset immediately .

Suitable up to category 2; SIL1;PLd reachable

24V AC/DC

A2(-)

Y1

Y2

A1(+)

START

S1

41

13

33

23