d) RS-NAGA / RS-NAGAO

(RS-NAGA : with start control)

(RS-NAGAO: without start control)


Dual channel emergency stop

(without opposite polarity between channels)


By pressing the start button, the unit will be
activated. For this application, terminals X1/S22
and K12 are not bridged. Instead, a redundant
emergency stop contact is applied. In this
application a fault in the emergency stop is
detected.
If using RS-NAGAO with automatic start the two
emegency stop contact must be used not only
one.

Suitable up to category 3; SIL2; PLd reachable

Dual channel emergency stop (with opposite

polarity between channels)


In this application are the terminal connections
PE and K12,S12 changed. By pressing the start
button the device will be activated. Terminals 13-
14, 23-24 and 33-34 close, and contact 41-42
opens. Pressing the emergency stop- or off-
button initiates a stop and the outputs open
immediately.

Suitable up to category 4; SIL3; PLe reachable

Dual channel emergency stop with external

contact extension (t wo contactors), contact

monitoring and opposite polarity between

channels

This application uses two external contactors with
positive guidance. Each normally closed contact
of these external contactors must be connected in
series to the start button to the terminals X1/S22
and X2. The function is similar to application no 2.
Through the switch S ext. the external contactors
can be operated or turned off at any time if the
RS-NAGA / RS-NAGAO is activated.

Suitable up to category 4; SIL3; PLe reachable

Dual channel protection door mo nitoring

without opposite polarity between channels


With the dual channel protection door monitoring
terminals X1/S22 and K12 are not bridged. The
function is like application no 1. In this application
a fault in the protection door monitoring switch will
be detected.

Suitable up to category 3; SIL2; PLd reachable

X2

S11

K12

X1/

S22

Fr

ei

ga

be

S1

S2

S12

PE

13

33

23

41

Not-

STOP

Halt/
E-

S11

K12

X2

X1/

S22

PE

START

Aus/

Off

Not-

STOP

Halt/

E-

S11

S12

X2

X1/K12

S22

PE

START

Not-

STOP

Halt/
E-

S

ext.

ext.

U

S11

S12

X2

X1/K12

S22

ext.

K2

K1

ext.

PE

13

14

14

START

K

1

ex

t.

K

2

ex

t.