Function same as in application 9, Category 4, ple, sil 3 reachable – NORSTAT Safety Relays Benutzerhandbuch

Seite 96

Advertising
background image



application guide safety relays from riese electronic page

92

Monitoring of a clocked safety switch with automatic start and

supply of the clocked safety switch by an external power supply.

The clocked safety switch is supplied by an external power supply. The
negative pole of the clocked safety switch is connected additionally to terminal
S36.

Function same as in application 9

Category 4, PLe, SIL 3 reachable

S32 S33

S22

S12

S11

S21

S34

A1

Kext

S35

S36

A2

+24V DC

0V DC

L+

L-

0V DC

+24V DCx

TE

A

Monitoring of a clocked safety switch with monitored start and

supply of the clocked safety switch by an external power supply.

The clocked safety switch is supplied by an external power supply. The
negative pole of the clocked safety switch is connected additionally to terminal
S36.
Function same as in application 10

Category 4, PLe, SIL 3 reachable

S22

S12

S11

S21

A1

S35

S36

A2

+24V DC

0V DC

S32 S33

S34

Kext

Start

L+

L-

+24V DCx

0V DC

TE

A

Contact expansion with SAFE X4.1 in applications with monitored

start

For monitoring the contacts of the expansion are linked into the feedback
control loop S33/S34 of the SAFE FLEX.

In the case of protected laying of the wires and exclusion of parasitic
voltage between U1 and K1/K21 the expansion is qualified up to safety
category 4

Category 4, PLe, SIL 3 reachable

A1

A2

+24V DC 0V DC

S32 S33

S34

Start

U22

K1

K21

U1

Y1

Y2

13

14

23

24

A1

A2

+24V DC

0V DC

13

14

23

24

33

34

43

44

+ Eingangsbeschaltung

+ inputs wiring

SAFE FLEX

SAFE X4.1

Contact expansion with SAFE X4 in applications with automatic

start

For monitoring the N/C contacts of the expansion are linked into the feedback
control loop of the SAFE FLEX.

Category 4, PLe, SIL 3 reachable

A1

A2

+24V DC

0V DC

S32 S33

S34

U22

K1

K21

U1

Y1 Y2

13

14

23

24

A1

A2

+24V DC

0V DC

13

14

23

24

33

34

43

44

+ Eingangsbeschaltung

+ inputs wiring

SAFE FLEX

SAFE X4

NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866

Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com

Advertising