application guide safety relays from riese electronic

page 74

Dual channel protection door monitoring with

start monitoring and opposite polarity

between channels


If the safety switches S1 and S2 are closed, the
output contacts remain unchanged. Through a
short operation of the release switch the contacts
13-14, 23-24 and 77-78 close after the releasing
of the switch with a delay of approximately 100
ms.
After opening the safety switches the contacts
13-14 and 23-24 return to their normal position
without delay. The contact 77-78 remains open
during the selected time delay.

up to category ...

immediate switching: 4; SIL3; PLe reachable,

time delayed output: 3; SIL2; PLd reachable






Dual channel protection door monitoring with

automatic activation and with opposite

polarity between channels


In this application the activation of the device
works automatically, since the terminals T11 and
T34/X1 are bridged. If the protection door
switches are closed, the contacts close with a
delay of approximately 100 ms. After opening the
protection door switches the contacts 13-14 and
23-24 return to their normal position without
delay. The contact 77-78 remains open during the
selected time delay.

up to category ...

immediate switching: 4; SIL3; PLe reachable,

time delayed output: 3; SIL2; PLd reachable




T34/

K21

T11

X1

T12

X2

K22

S1

S2

Freigabe/

release

PE/

B2

23

13

77












13

K21

T11

T34/

X1

T12

X2

K22 PE/

B2

S1

S2

23

77