C) rs-nagt / rs-nagt.1 – NORSTAT Safety Relays Benutzerhandbuch

Seite 75

Advertising
background image

application guide safety relays from riese electronic

page 71

T34/

T11

K21

X1

T12

X2

13

PE/
B2

K22

23

77

START

Not-
Halt/
E-
STOP

c) RS-NAGT / RS-NAGT.1

Single channel emergency stop button

(without opposite polarity between channels)


With power applied to the unit, pressing the start
button activates the unit. Safety outputs 13-14,
23-24 and 77-78 close. Pressing the emergency
stop initiates a stop and outputs 13-14 and 23-24
open
immediately. The contact 77-78 remains closed
during the selected time delay. In this application,
the demand of redundancy in the emergency stop
is not accomplished.

Suitable up to category 2; SIL1; PLd reachable







Dual channel emergency stop (without

opposite polarity between channels)


For this application, terminals T12 and K22 are
not bridged. Instead, a redundant emergency
stop contact is applied. The function is shown in
application No. 1. In this application a fault in the
emergency stop is detected.

Suitable up to category 3; SIL2; PLd reachable






Dual channel emergency stop (with opposite

polarity between channels)


For this application, the terminal connection
PE/B2 and K21 are changed. By pressing the
start button the device will be activated. Terminals
13-14, 23-24 and 77-78 close. Pressing the
emergency stop initiates a stop and outputs 13-
14 and 23-24 open immediately. The contact 77-
78 remains closed during the selected time delay.

up to category …

immediate switching: 4; SIL3; PLe reachable,

time delayed output: 3; SIL2; PLd reachable

Not-

STOP

E-

Halt/

T34/

T11

X1

K22

X2

T12 K21 PE/

B2

13

23

77

S

TA

R

T

T34/

X1

T11

K22

X2

K21

T12

PE/
B2

13

23

77

S

TA

R

T

Not-
Halt/
E-
STOP

NORSTAT INC. 300 Roundhill Dr. Rockaway, NJ 07866

Tel: 973-586-2500 Fax: 973-586-1590 www.norstat.com

Advertising