Switches the device into the automatic start mode – NORSTAT Safety Relays Benutzerhandbuch

Seite 93

Advertising
background image



application guide safety relays from riese electronic page

89

immediately, the contacts 13-14 and 23-24 are opened. The auxiliary output
S31 becomes inactive.
A reset can not be effected until both safety gate switches are opened
simultaneously.
General information:
For this operation mode the terminals S35/S36

must be bridged. For the safety

gate function the simultaneity* of the channels is infinite. The two channels
must not have different signals when the supply-voltage is switched on. That
means both contacts of the safety gate switch have to be opened or closed.

In case of a faulty input-wiring, the device will switch to the FAIL-SAFE
mode (safety-switch-off).

Category: 4 , PL e, SIL 3 reachable

S32 S33

S22

S12

S11

S21

S34

A1

Kext

S35 S36

A2

+24V DC

0V DC

Two-hand application

If the push buttons S1 and S2 are pressed simultaneously, the

outputs 13-14, 23-24 are closed and output S31 is turned on.

After releasing one or both push buttons the outputs 13-14 and 23-24 are
opened and the output S31 is turned off. Only after releasing both push buttons
a new cycle can be started.
By asynchronous actuation (t>0,5s) the outputs are not released. The outputs
13-14 and 23-24 remain opened, output S31 remains turned off.
General information

For this operation mode the terminals S35/S36

must be bridged. The time

between pressing both switches is limited to max. 0,5s. After exceeding this
time a new cycle can only be started after releasing both push buttons. In the
moment of turning on the supply voltage the push buttons must not be
actuated.

In case of a faulty input-wiring, the device will switch to the FAIL-
SAFE mode (safety-switch-off).

For type 3c, Ple, SIL 3 reachable

S32 S33

S22

S12

S11

S21

S34

A1

Kext

S35 S36

A2

+24V DC

0V DC

S36

S1

S2

Dual channel application for connecting OSSD contacts (pnp) of

an ESPE with automatic start and supply of the ESPE by the SAFE

FLEX.

OSSD1 and OSSD2 have to be connected to the input circuits (S11/S12 and
S21/S22). The bridge (or the feedback control loop) S32/S33

switches the

device into the automatic start mode.

The activation of the outputs

results from the activation of the outputs of the ESPE (OSSDs outputs have
high-signal). When the optical way of the light barrier is interrupted the OSSD
outputs of the ESPE turn off (low signal) and the safety outputs of the SAFE
FLEX fall off into the initial state. The contacts 13-14 and 23-24 are opened.
The auxiliary output S31 is inactive.
The power supply of the light barrier/ light curtain is provided by the SAFE
FLEX (negative pole to S36, positive pole to S21, I

max

= 50mA)

General information:
For this operation mode the terminals S35/S36 must not be bridged. The
simultaneity is defined by the high signals at the inputs S12 and S22. The
high-signal at the input S22 may be activated maximally 0,5s after the high-
signal at the input S12. A High-signal at the entrance S12 can be activated as
desired after the High-signal at S22. After exceeding the simultaneity a new
cycle can only be started after deactivating the OSSDs. The safety inputs

S32 S33

S22

S12

S11

S21

S34

A1

Kext

S35

S36

A2

+24V DC

0V DC

L+

OSSD1 OSSD2

L-

BWS / ESPE