application guide safety relays from riese electronic

page 64

2 Product application for

- emergency stop relay

- safety gate monitoring relay

-

safety mats and safety contact edges

a) SAFE CM

(SAFE CM is adapted for safety gates and safety bars, also with load resistance)

2-channel application with auto-start and broken wire check.
The safety mat switch must close the input circuits (S11/S12,
S21/S22), and the S11-S34 has to be brigded for auto-start
configuration. The bridge between S21-S32 activates stand-alone
application (no AND connection). The outputs will be activated when
the contact areas of the mat are not connected (mat not entered)

up to category 4; SIL3; PLe reachable

S34

S35

S22

S12

S11

S21 S32

S33

S36

S37

2-channel application with monitoring of reset circuit and broken

wire check

.

The safety mat switch must close the input circuits (S11/S12,
S21/S22. The outputs will be activated when the contact areas of the
mat are not connected (mat not entered) and the start button is
pressed and released.

up to category 4; SIL3; PLe reachable

S35

S34

S22

S12

S11

S21 S32

S33

S36 S37

1-channel application with auto start and broken wire check.

The mat with final resistance must be connected to S36 and S37. Auto start
is activated by bridge between S34-S11.
The outputs will be activated when the contact areas of the mat are not
connected (mat not entered)

For monitoring of the external conductors, the NC contacts of the
force guided contactors must be attached in series to the start circuit

up to category 4; SIL3; PLe reachable

S33

S36 S37

14

34

K1

K2

A2

K1

K2

S34

S22

S12

S11

S21 S32

8k2

K1

K2

S35

1-channel application with monitoring of reset circuit and broken

wire check.

The mat with final resistance must be connected to S36 and S37.

The safety mat switch must close the input circuits (S11/S12,
S21/S22. The outputs will be activated when the contact areas of the
mat are not connected (mat not entered) and the start button is
pressed and released.

up to category 4; SIL3; PLe reachable

S35

S33

S36 S37

S22

S12

S21 S32

8k2

S34

S11