6.3 Device profile specific objects
Setting and interrogating the sensor-specific values. The following indices are supported:
Object Name
6110
Sensor type
6112
Operating mode
6125
Autozero
6131
Physical unit PV
6132
Decimal unit PV
6150
Status of measurement
7130
Process value 16bit
7133
Interrupt delta input 16bit
8130
Process value 24bit
8133
Interrupt delta input 24bit
6.3.1
Sensor type
Read sensor type (object 6110h):
ID
DLC
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
600h + ID
8
40h
10h
61h
01h
0
0
0
0
Response from CANopen strain link:
ID
DLC
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
580h + ID
8
4Bh
10h
61h
01h
46h
00h
0
0
Byte 5:
46h
strain link
The object 6110h is read only.
6.3.2
Operation mode
When delivered, the sensor is always in normal mode.
Read operation mode (object 6112h):
ID
DLC
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
600h + ID
8
40h
12h
61h
01h
0
0
0
0
Response from CANopen strain link:
ID
DLC
Byte1
Byte2
Byte3
Byte4
Byte5
Byte6
Byte7
Byte8
580h + ID
8
4Fh
12h
61h
01h
01h
0
0
0
Byte 5:
01h
Acquisition mode
02h – 09h
reserved
0Ah
(Adjust mode)
The object 6112h is read only.