Manual_CANopen_StrainLink_EN_V3_05.doc

56/65

Baumer

22.07.11/dam

Frauenfeld, Switzerland

7.5.3

Configuration mode direct connection (master sensor)

To use LSS the sensor has to be in the LSS configuration mode.
The sensor can be set into the LSS configuration mode as follows:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

7E5

8

04h

01h

0

0

0

0

0

0


The current set ID can be interrogated to test if the sensor has switched into the configuration mode:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

7E5

8

5Eh

0

0

0

0

0

0

0


Response from CANopen strain link:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

7E4

8

5Eh

01h

0

0

0

0

0

0


Example “ID 1“
Byte 2:

01h

accessed sensor has ID 1


If the sensor does not respond, the sensor does not support LSS or the baud rate is incorrect. For safe
access the service and its baud rates has to be tested.
Now the ID or the baud rate can be changed.

7.5.4

Configuration mode of a sensor in a network

With the following orders the sensor can be identified:
Transmission of vendor ID:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

7E5

8

40h

5Fh

00h

00h

00h

0

0

0


Vender ID:
Byte 1:

40h

System byte vender ID

Byte 2 – 5:

5F’00’00’00h

00’00’00’5F (LSB first)

Firma Baumer electric


Transmission of product code:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

7E5

8

41h

44h

0Dh

A8h

00h

0

0

0


Product code:
Byte 1:

41h

System byte product code

Byte 2 – 5:

44’0D’A8’00h

00’A8’0D’44 (LSB first)

11013444 in decimal


Transmission of revision number:

ID

DLC

Byte1

Byte2

Byte3

Byte4

Byte5

Byte6

Byte7

Byte8

7E5

8

42h

01h

02h

03h

00h

0

0

0


Revision number:
Byte 1:

42h

System byte revision number

Byte 2 – 5:

01’02’03’00h

00’03’02’01 (LSB first)

00030201h